ResQ-Window Vision Panel – BS EN 1634-1

Key Information
  • Curtain Types: Fire Curtains
  • Product Standards: BS EN 1634-1, BS EN 1634-3
  • Standards: EN - European
  • Orientations: Vertical
  • Integrity Ratings: Up to 120 mins
  • Radiation Ratings: Up to 30 mins
  • Special Features: Tested to BS EN 1634-1. 120 mins Integrity and can be installed into the FireMaster A1 fire curtain
fire icon Vertical icon 120 minutes fire rating

Quick Links
Sizes and Classification | Description | Downloads | Resources

Select your Product Standard:

BS EN 1634-1 UL 10D

Vertical - Single Roller 5m width x 8m drop (Maximum Size) E120 EW30 (E=Integrity, EW=Radiance)
Vertical - Single Roller 5.2m width x 7m drop (Maximum Size) E120 EW30 (E=Integrity, EW=Radiance)
Vertical - Single Roller 5.3m width x 6m drop (Maximum Size) E120 EW30 (E=Integrity, EW=Radiance)
Vertical - Single Roller 6m width x 5m drop (Maximum Size) E120 EW30 (E=Integrity, EW=Radiance)

 

The ResQ-Window™ is a vision panel window for fire curtains which can be installed into a Coopers Fire fire curtain allowing building occupants and first responders to see through the curtain after it has been deployed.

Applications: Lobbies and Receptions, Opening in Walls, Egress and Corridor Separations, Compartmentation, Stairs and Escalators, Lifts and Lift Lobbies, Protected Means of Escape

ResQ-Window™ is a patented translucent fire proof flexible material that can be installed into a Coopers Fire fire curtain allowing building occupants and first responders to see through the curtain after it has been deployed.

Patent pending GB2575746Click Here to find out more

ResQ-Window™ can withstand temperatures in excess of 1000oC with 2 hours integrity (E120) and tested to BS EN 1634-1. The curtain with a vision panel is designed for:

  • Escape routes incorporating doorways and corridors
  • Lift openings and lobbies
  • Areas where Fire Marshals and the Fire and Rescue Service may need to assess prior to entry

BS 9999 and Approved Document B both reference the requirement and benefits of vision panels used in fire safety in occupied buildings.

The ResQ-Window™ can be installed into a single roller fire curtain only (it is not available on overlapping fire curtains) and  can be positioned to allow a low and high level view through the curtain if required.

Approximate size of window = 415mm (h) x 270mm (w)

Minimum widths achievable are as follows:
T Bar – 1300mm
Jumbo Bar – 900mm

FOR FIRE PROTECTION CLASSES EXPLAINED – click here

All fire and smoke curtains are manufactured to bespoke sizes. To discuss your requirements GET IN TOUCH 