THESE TABLES WILL HELP ASSIST YOU WITH THE TYPE OF FIRE OR SMOKE CURTAIN PRODUCT REQUIRED.

BS 8524-1 FIRE CURTAINS

Active fire curtain barrier assemblies. Specification.
Products suitable for the UK and other countries

Product Name Orientation Max Width and Max Drop Fire Classification Certifier Smoke Control

FireMaster A1 Fire Curtain

Vertical - Single Roller 5m x 8m
6m x 5m
E180 EW30
E180 EW30
IFC Certification
Warringtonfire
Yes*

ResQ-Window Vision Panel

Vertical - Single Roller TBC E120 EW30 TBC Yes*

FireMaster A1 Fire Curtain

Vertical - Overlapping Rollers Unlimited x 6m
27.5m x 8m
E120 EW30 IFC Certification No

FireMaster Plus2 Fire Curtain

Vertical - Single Roller 5m x 8m E180 EW90 IFC Certification Yes*

FireMaster Plus2 Fire Curtain

Vertical - Wide Single Roller Contact Coopers Fire Contact Coopers Fire IFC Certification Yes*

FireMaster Concertina Fire Curtain

Concertina - Open Unlimited x 5m E180 EW30 IFC Certification No

FireMaster Concertina Fire Curtain

Concertina - Open Unlimited x 8m E120 EW30 IFC Certification No

FireMaster Concertina Fire Curtain

Concertina - Closed Unlimited x 5m E240 EW30 IFC Certification No

FireMaster Concertina Fire Curtain

Concertina - Closed Unlimited x 8m E120 EW30 IFC Certification No

ViiFire A1 Fire Curtain

Vertical - Single Roller 5m x 3m E120 EW30 IFC Certification Yes*

ViiFire iZone Fire Curtain

Vertical - Single Roller 4m x 4m E180 EW60 IFC Certification Yes*

* Approved to BS EN 1634-3, Fire resistance and smoke control tests for door and shutter assemblies, openable windows and elements of building hardware. Smoke control test for door and shutter assemblies.

BS EN 1634-1 FIRE CURTAINS

Fire resistance and smoke control tests for door and shutter assemblies, openable windows and elements of building hardware. Fire resistance test for door and shutter assemblies and openable windows
Products suitable for the UK, Europe and other countries

Product Name Orientation Max Width and Max Drop Fire Classification Certifier Smoke Control

FireMaster A1 Fire Curtain

Vertical - Single Roller 5m x 8m
6m x 5m
E120 EW30
E180 EW30
Warringtonfire Yes*

FireMaster A1 Fire Curtain

Vertical - Single Roller 7m x 7m E180 EW30 Warringtonfire Yes*

FireMaster A1 Fire Curtain

Vertical - Overlapping Roller Unlimited x 6m E120 EW30 Warringtonfire No

ResQ-Window Vision Panel

Vertical - Single Roller 5m x 8m E120 EW30 Warringtonfire Yes*

FireMaster Plus2 Fire Curtain

Vertical - Single Roller/Wide Single Roller 7m x 7m E120 EW90 Warringtonfire Yes*

FireMaster Plus2 Fire Curtain

Vertical - Single Roller/Wide Single Roller 7.8m x 6.2m E120 EW90 Warringtonfire Yes*

FireMaster Plus2 Fire curtain

Vertical - Single Roller/Wide Single Roller 7m x 4m E180 EW90 Warringtonfire Yes*

FireMaster Cleanroom Fire Curtain

Vertical - Single Roller 3m x 4m E120 EW120 Warringtonfire
Fraunhofer
No

FireMaster Cleanroom Fire Curtain

Vertical - Single Roller 4m x 4m E90 EW90 Warringtonfire
Fraunhofer
No

FireMaster Marine Fire Curtain

Vertical - Single Roller 2.4m x 2.692m A-0 Lloyds Register No

FireMaster Horizontal Simplex Fire Curtain

Horizontal - Simplex 7m x 7m E120 Warringtonfire No

FireMaster Horizontal Duplex Fire Curtain

Horizontal - Duplex Contact Coopers Fire Contact Coopers Fire Warringtonfire No

FireMaster 4/1000 Fire Curtain

Vertical - Single Roller 7m x 8m E240 EW30 Warringtonfire Yes*

FireMaster 4/1000 Fire Curtain

Vertical - Overlapping Roller Unlimited x 8m E120 EW30 IFC Certification No

FireMaster Superplus Fire Curtain

Vertical - Single Roller Unlimited x 3m E120 EI120 (through assessment) No

FireMaster Concertina Open Fire Curtain

Concertina - Open Unlimited x 5m E180 EW30 IFC Certification No

FireMaster Concertina Open Fire Curtain

Concertina - Open Unlimited x 8m E120 EW30 IFC Certification No

FireMaster Concertina Closed Fire Curtain

Concertina - Closed Unlimited x 5m E240 EW30 IFC Certification No

FireMaster Concertina Closed Fire Curtain

Concertina - Closed Unlimited x 8m E120 EW30 IFC Certification No

* Approved to BS EN 1634-3, Fire resistance and smoke control tests for door and shutter assemblies, openable windows and elements of building hardware. Smoke control test for door and shutter assemblies.

UL FIRE AND DRAFT CURTAINS

UL 10D – Standard for Fire Tests of Fire-Protective Curtain Assemblies
Read more about this standard.

UL 1784 – Standard for Air Leakage Tests of Door Assemblies and Other Opening Protectives
Read more about this standard.

Products suitable for the US, Middle East and other countries

Product Name Orientation Max Width and Max Drop Fire Classification Certifier Smoke Control

FireMaster A1 Fire Curtain

Vertical - Single/Overlapping Rollers Unlimited x 8m 240 minutes UL Yes

ResQ-Window Vision Panel

Vertical - Single Roller 2.6m x 2.8m 180 minutes UL Yes

FireMaster 4/1000 Fire Curtain

Vertical - Single/Overlapping Roller Unlimited x 8m 180 minutes Intertek Yes

FireMaster Egress Fire Curtain

Vertical - Single Roller Unlimited x 8m 180 minutes Intertek Yes

FireMaster Concertina Open Fire Curtain

Concertina - Open Unlimited x 8m 240 minutes UL No

FireMaster Concertina Closed Fire Curtain

Concertina - Closed Unlimited x 8m 240 minutes UL No

SmokeStop Draft Curtain

Vertical - Single/Overlapping Rollers Unlimited x 8m N/A Intertek No

SmokeStop Egress Smoke Curtain

Vertical - Single/Wide Single Roller 18m x 7m N/A Intertek Yes

FireMaster Concertina Egress Fire Curtain

Concertina - Closed/Open Unlimited x 8m 120 minutes UL No

BS EN 12101-1 SMOKE CURTAINS

Smoke and heat control systems. Specification for smoke barriers.
Products suitable for the UK and other countries

Product Name Orientation Max Width and Max Drop Certifier Fire Resistance

SmokeStop D600A Smoke Curtain

Vertical - Single Roller 6m x 4m IFC Certification 150 minutes

SmokeStop D600A Smoke Curtain

Vertical - Overlapping Rollers Unlimited x 10.5m IFC Certification 150 minutes

SmokeStop D600A Smoke Curtain

Vertical - Side by Side Overlapping Unlimited x 6.7m IFC Certification 150 minutes

SmokeStop DH60 Smoke Curtain

Vertical - Single Roller 6m x 4m IFC Certification 60 minutes (DH60)

SmokeStop DH60 Smoke Curtain

Vertical - Overlapping Rollers Unlimited x 10.5m IFC Certification 60 minutes (DH60)

SmokeStop Concertina Open

Concertina - Open Unlimited x 6m Warringtonfire 60 minutes (DH60)

SmokeStop Concertina Closed

Concertina - Closed Unlimited x 6m Warringtonfire 60 minutes (DH60)

SmokeStop EvacU8 Smoke Curtain

Vertical - evacU8 Unlimited x 6.7m IFC Certification 150 minutes